Step 2.6: Activating and transferring configuration

  1. Chose EtherCAT bus
  2. Generate allocation
    (Generate allocation between 2 process images)
  3. Check configuration
    (Plausibility check)
  4. Activate configuration
    (Save and activate current configuration)

 

Check whether the 'pre-operational' state is reached.

 

Generate the safety configuration and transfer it to the SafePLC EL6900.

 

The specific serial number is used for entering the password!

 

User name: Administrator

Serial No.: see previous image

Password: TwinSAFE

 

The procedure is finished by pressing the 'Start' button.

 

Following enter password: TwinSAFE

 

Restart system